ASENS-CPIRHS-PRO

Recessed High Sensitivity Passive Infrared Dimming Detector

ASENS-CPIRHS-PRO

The ASENS-CPIRHS-PRO high sensitivity passive infrared presence or absence detector provides automatic control of lighting loads in buildings and interior spaces with high ceilings. The ASENS-CPIRHS-PRO is typically installed in warehouses, sports halls and atria and is used in other applications where mounting heights are too high for standard detectors.

The ASENS-CPIRHS-PRO has a two channel capability for use with both digital dimming and switched lighting loads. For example, in an atria, the window row of luminaires can be dimmed down according to daylight detection and the rest of the luminaires are switched on and off only. Two input terminals can be used to manually override the dimming levels and override the luminaires on and off.

The detector use a highly sensitive passive infrared sensor in a precision dome lens, which enables the ASENS-CPIRHS to reliably detect movement over large areas. Mounting heights of up to 15m can be accomodated.

The detection area can be customised (in slot shaped or radial patterns) using a highly innovative clip-on masking shield. The two part mask is supplied as standard.

The ASENS-CPIRHS-PRO can be flush fitted in to ceilings that have sufficient void space or can be mounted directly to a solid ceiling or slab using the ASENS-CPIR-BOX.

The functionality of the ASENS-CPIRHS-PRO is controlled by a number of parameters which can be accessed by the ASENS-CHSLCD or the ASENS-CHS5 handheld infrared remote controls.

Order Code

  • ASENS-CPIRHS-PRO

Accessories

Detection

H D

Walking Across Detector Area

D9m16m26m40m
H3m6m10m15m

Walking Towards Detector Area

D8m12m20m30m
H3m6m10m15m

Dimensions

ASENS-CPIRHS-PRO Dimensions
D H1 H2 C
88 49 63 64

Technical

  • Avoid positioning the detector where direct sunlight may enter the sensor element
  • Do not install sensor within 1m of any lighting
  • Do not install sensor within 1m of forced air heating or ventilation
  • Do not fix the sensor to an unstable or vibrating surface
Supply230V AC 50Hz
Circuit Protection10A
Max Load Channel 110A
Max Load Channel 2Maximum number of digital dimming ballasts = 10 (relay enabled)
Maximum number of digital dimming ballasts = 20 (relay disabled)
Dimming output is not SELV, Mains rated cabling must be used
Power ConsumptionOn = 800mW
Off = 299mW
Weight0.2kg
TimeoutAdjustable 10sec to 99min
Terminal Capacity2.5mm²
Temperature-10°C to 35°C
Humidity5% to 95% non-condensing
Material (casing)Flame Retardant ABS and Polycarbonate Class 2
IP RatingIP40 without gasket
IP44 with gasket
Compliance and StandardsEMC-2004/108/EC
LVD-2006/95/EC
CE Marked

Wiring

Wiring Diagram 1 : Switch And Dim Together

ASENS-CPIRHS-PRO Wiring Diagram

Switches the luminaire with occupancy detection and maintains illuminance. Dims and switches using the centre biased retractive switch.

Wiring Diagram 2 : Switch And Dim Together

ASENS-CPIRHS-PRO Wiring Diagram

Where there is a requirement fo the luminaires to stay on dim instead of turning off, then use the dimming pair to both switch and dim. A value greater than zero in the 'off value' parameter will achieve a minimum dimmed level for the off state.

Wiring Diagram 3 : Switch And Dim Separately

ASENS-CPIRHS-PRO Wiring Diagram

Switches both channels with occupancy, maintains illuminance, dims and switches the dimming channel using the single position retractive switch 2. Switches the switching channel on and off using the single position switch 1.

Wiring Diagram 4 : Two Channel, Common Switch

ASENS-CPIRHS-PRO Wiring Diagram

Switches both channels with occupancy, maintains illuminance, dims and switches the dimming channel using the centre biased retractive switch.

Wiring Diagram 5 : Single Switch Only

ASENS-CPIRHS-PRO Wiring Diagram

Switches channel 1 only with occupancy, optional override switch, no dimming output.