DDC313

Recessed DALI Microwave Detector

DDC313

The DDC313 Low Profile Microwave Detector provides occupancy detection for the automatic control of DALI lighting loads.

The DDC313 detects movement using a highly sensitive microwave detector. It works by emitting low-power microwave signals and measuring the reflections as the signals bounce off moving objects.

When an area is no longer occupied, the load will switch off after a certain time. This sensitivity and timeout period are configured using the lighting system design and control software.

Key Features

  • Microwave sensor detects movement within the detection range allowing load control in response to changes in room occupancy

Order Code

  • DDC313

Accessories

  • Surface Mounting Box for DDC311, DDC313, ASENS-CPIR and ASENS-C6MW
  • Single DALI Network Router
  • Twin DALI Network DALI Router
  • Twin DALI Network Router with DMX and S-DIM

Detection

H D
D H
12–16m 2.8m

Dimensions

DDC313 Dimensions
D H C
76 65 64

Installation Notes

  • Position the sensor so that the occupants of the room are normally inside the detection zone
  • Do not install the sensor within 1m of any lighting, forced air heating, or ventilation equipment
  • Do not fix the sensor to an unstable or vibrating surface
  • Install the unit as far away as possible from the surface of metal objects
  • The detection pattern illustrated is based on a mounting height of 2.8m. A lower mounting height will decrease the overall size of the detection zone

Technical

Connections
External Power / DALIRemoveable 2 pole connectors
0.5mm²–2.5mm² solid or stranded wire
All cables must be mains rated
Power
DALI Supply Input13–22.5V
DALI consumption20mA
External Power (optional)12–24V, 0.5W
DALI consumption is less than 2mA when external power supply is used
Microwave Operating Frequency5.8GHz
Mechanical
Material (casing)Non-flammable ABS
Finish / ColourMatt / White
Weight90g
IP RatingIP30
Ambient Temperature0°C to 35°C
Storage Temperature-10°C to 70°C
Relative HumidityMax 95%, non-condensing
Compliance and Standards
EMC ImmunityEN61000-6-1
EMC EmissionsEN6100-6-3
SafetyEN60730-1
EnvironmentComplies with WEEE and RoHS directives